Specification
EF6012 | |
---|---|
Input | 90 ~ 264 V AC 1A 47 … 63 Hz |
Output | 13.8 V, 4 A |
Battery charge | 13.8 V, 1 A |
Rated power | 60 W |
Efficiency | main power: 86%;
battery power: 99% |
Charging method | constant current/ constant voltage (CC/CV) |
Protection | from short circuit; output overload; overvoltage; from deep battery discharge; from running on a discharged battery. |
Battery cutoff voltage | 10.8 V |
Start by battery | at voltage > 12.0 V |
Battery type | Lead-acid 12 V (VRLA - AGM/GEL) |
Recommended battery capacity | 7 … 20 Ah |
Working temperature | 0 … +60 °C (+32 … +140 °F) |
Working humidity | up to 90%, non-condensing |
Dimentions | 105×52×32 mm (4.13×2.05×1.26″) |
Weight | 125 g (4.41 oz) |